Notes from the team
Drawn to scale · 6.00 × 5.00 m, 30 m² · 4 seats · Outlets: Type G sockets; UK and Ireland plates, 86 and 146 mm wide, 450 mm up to the centre (house default; the space type gives no height) · Space size varies by office; 6 × 5 m shown · Desk for one or two, lounge seating, signage 65 in shown
Compared against
Standard, with the door and building systems wired: The standard reception, with its door controller, CCTV camera and an environment sensor each on a data outlet, so they sit on the Security and Building VLANs.
- Required devices
- All recorded
- Optional fitted
- 2 of 3
- Wiring
- Checks pass
Fitted: Wall plate where a laptop plugs in (HDMI or USB-C); sends to the display over HDBaseT, HDBaseT receiver at the display.
Lifecycle
- In service
- 7
Cable tests
Restricted: rack and switch portsAll 7 links passed certification · closest margin 3.3 dB · last tested 13 Oct 2026
| Link | Outlet | Cable | Length | Result | Margin | Tested |
|---|---|---|---|---|---|---|
| DUB-3.21-R1-U06-P01 | Behind the display, 1 | Cat6A | 27 m | Pass | 6.18 dB | 14 Feb 2022 |
| DUB-3.21-R1-U06-P02 | Behind the display, 2 | Cat6A | 27.22 m | Pass | 3.34 dB | 14 Feb 2022 |
| DUB-3.21-R1-U06-P03 | Behind the display, 3 | Cat6A | 27.39 m | Pass | 4.63 dB | 14 Feb 2022 |
| DUB-3.21-R1-U06-P04 | Set per project, 1 | Cat6A | 28.33 m | Pass | 5.51 dB | 14 Feb 2022 |
| DUB-3.21-R1-U06-P41 | Ceiling, 1 | Cat6A | 19.54 m | Pass | 5.12 dB | 13 Oct 2026 |
| DUB-3.21-R1-U06-P42 | At the door, 1 | Cat6A | 23.74 m | Pass | 4.86 dB | 13 Oct 2026 |
| DUB-3.21-R1-U06-P43 | Ceiling, 2 | Cat6A | 19.54 m | Pass | 5.41 dB | 13 Oct 2026 |
From the cabling contractor's certification report, recorded on each run (made up for the demo). A margin under 3 dB passes but is worth a look.
Upkeep
Licences from the licence portals
1 licence, each with a seat for this space
- BSN.cloudDevice management · renews 7 Mar 2027 (in 139 days)
Outlets
For this space| Service | Where | How many | Serves | Provided by |
|---|---|---|---|---|
| Power | Behind the display | 4 | display, signage player, spare, spare | IT |
| Data | Behind the display | 3 | display, signage player, spare | IT |
| Data | Set per project | 1 | wall plate for a laptop (optional)Terminated as a plug so the installer can test it | IT |
| Power | Set per project | 1 | wall plate (optional)The wall plate draws 5 V DC at 390 mA | IT |
| Data | Ceiling | 2 | CCTV camera, environment sensor | IT |
| Data | At the door | 1 | door controller | IT |
Wiring
3 signal cables, 8 to outletsIncludes the optional kit fitted here.
List every cable
| Cable | From | To |
|---|---|---|
| HDMI | Signage player, hdmi-out-1 | Display, hdmi-in-1 |
| Cat 6A | Wall plate where a laptop plugs in (HDMI or USB-C); sends to the display over HDBaseT, hdbaset-1 | HDBaseT receiver at the display, hdbaset-1 |
| USB-C | Wall plate where a laptop plugs in (HDMI or USB-C); sends to the display over HDBaseT, usb-c-1 | Laptop |
| Cat 6 | Display, lan-1 | Data outlet 1, behind the display |
| Cat 6 | Signage player, lan-1 | Data outlet 2, behind the displayPoE+ powers the player |
| Power | Display, power-in | Power outlet 1, behind the display |
| Power | HDBaseT receiver at the display, power-in | Power outlet 4, behind the display |
| Power | Wall plate where a laptop plugs in (HDMI or USB-C); sends to the display over HDBaseT, power-in | Power outlet 1, set per project |
| Cat 6 | CCTV camera, lan-1 | Data outlet 1, ceilingPoE powers the camera |
| Cat 6 | Temperature, humidity and CO2 sensor for the building management system, lan-1 | Data outlet 2, ceilingPoE powers the sensor |
| Cat 6 | Door controller for the office entrance (badge readers and the door release), lan-1 | Data outlet 1, at the doorPoE powers the controller and its readers |