Notes from the team
What's installed
24 devicesEach desk has
| Desk | Hub monitor | Second monitor, fed over DisplayPort from the hub monitor | Stage |
|---|---|---|---|
| Desk 01 | DEMO-NYC-000793AG-000793 | DEMO-NYC-000794AG-000794 | In service |
| Desk 02 | DEMO-NYC-000795AG-000795 | DEMO-NYC-000796AG-000796 | In service |
| Desk 03 | DEMO-NYC-000797AG-000797 | DEMO-NYC-000798AG-000798 | In service |
| Desk 04 | DEMO-NYC-000799AG-000799 | DEMO-NYC-000800AG-000800 | In service |
| Desk 05 | DEMO-NYC-000801AG-000801 | DEMO-NYC-000802AG-000802 | In service |
| Desk 06 | DEMO-NYC-000803AG-000803 | DEMO-NYC-000804AG-000804 | In service |
| Desk 07 | DEMO-NYC-000805AG-000805 | DEMO-NYC-000806AG-000806 | In service |
| Desk 08 | DEMO-NYC-000807AG-000807 | DEMO-NYC-000808AG-000808 | In service |
| Desk 09 | DEMO-NYC-000809AG-000809 | DEMO-NYC-000810AG-000810 | In service |
| Desk 10 | DEMO-NYC-000811AG-000811 | DEMO-NYC-000812AG-000812 | In service |
| Desk 11 | DEMO-NYC-000813AG-000813 | DEMO-NYC-000814AG-000814 | In service |
| Desk 12 | DEMO-NYC-000815AG-000815 | DEMO-NYC-000816AG-000816 | In service |
Compared against
Dual 27 inch: A 27 inch hub monitor plus a second 27 inch monitor daisy-chained from it.
- Required devices
- All recorded
- Wiring
- Checks pass
Lifecycle
- In service
- 24
Cable tests
Restricted: rack and switch portsAll 24 links passed certification · closest margin 2.5 dB · last tested 6 Oct 2026
| Link | Outlet | Cable | Length | Result | Margin | Tested |
|---|---|---|---|---|---|---|
| NYC-21.23-R1-U26-P29 | Desk 01/data/table top#1 | Cat6A | 41.11 m | Pass | 4.27 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P30 | Desk 01/data/table top#2 | Cat6A | 41.1 m | Pass | 5.85 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P31 | Desk 02/data/table top#1 | Cat6A | 42.75 m | Pass | 5.62 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P32 | Desk 02/data/table top#2 | Cat6A | 42.56 m | Pass | 2.80 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P33 | Desk 03/data/table top#1 | Cat6A | 44.1 m | Pass | 5.15 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P34 | Desk 03/data/table top#2 | Cat6A | 44.35 m | Pass | 2.59 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P35 | Desk 04/data/table top#1 | Cat6A | 41.31 m | Pass | 3.50 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P36 | Desk 04/data/table top#2 | Cat6A | 41.33 m | Pass | 3.19 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P37 | Desk 05/data/table top#1 | Cat6A | 42.55 m | Pass | 5.47 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P38 | Desk 05/data/table top#2 | Cat6A | 42.51 m | Pass | 6.49 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P39 | Desk 06/data/table top#1 | Cat6A | 44.33 m | Pass | 3.59 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P40 | Desk 06/data/table top#2 | Cat6A | 44.12 m | Pass | 2.51 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P41 | Desk 07/data/table top#1 | Cat6A | 44.24 m | Pass | 6.21 dB | 6 Oct 2026 |
| NYC-21.23-R1-U26-P42 | Desk 07/data/table top#2 | Cat6A | 44.37 m | Pass | 4.76 dB | 6 Oct 2026 |
| NYC-21.23-R1-U22-P01 | Desk 08/data/table top#1 | Cat6A | 46.17 m | Pass | 6.34 dB | 6 Oct 2026 |
| NYC-21.23-R1-U22-P02 | Desk 08/data/table top#2 | Cat6A | 45.96 m | Pass | 3.08 dB | 6 Oct 2026 |
| NYC-21.23-R1-U22-P03 | Desk 09/data/table top#1 | Cat6A | 47.42 m | Pass | 4.94 dB | 6 Oct 2026 |
| NYC-21.23-R1-U22-P04 | Desk 09/data/table top#2 | Cat6A | 47.72 m | Pass | 3.94 dB | 6 Oct 2026 |
| NYC-21.23-R1-U22-P05 | Desk 10/data/table top#1 | Cat6A | 44.59 m | Pass | 5.64 dB | 6 Oct 2026 |
| NYC-21.23-R1-U22-P06 | Desk 10/data/table top#2 | Cat6A | 44.52 m | Pass | 2.80 dB | 6 Oct 2026 |
| NYC-21.23-R1-U22-P07 | Desk 11/data/table top#1 | Cat6A | 46.01 m | Pass | 2.89 dB | 6 Oct 2026 |
| NYC-21.23-R1-U22-P08 | Desk 11/data/table top#2 | Cat6A | 46.2 m | Pass | 3.08 dB | 6 Oct 2026 |
| NYC-21.23-R1-U22-P09 | Desk 12/data/table top#1 | Cat6A | 47.73 m | Pass | 2.97 dB | 6 Oct 2026 |
| NYC-21.23-R1-U22-P10 | Desk 12/data/table top#2 | Cat6A | 47.68 m | Pass | 5.32 dB | 6 Oct 2026 |
From the cabling contractor's certification report, recorded on each run (made up for the demo). A margin under 3 dB passes but is worth a look.
Outlets
Per desk| Service | Where | How many | Serves | Provided by |
|---|---|---|---|---|
| Power | On the desk | 4 | monitor or dock, spare, spare, spare | IT |
| Data | On the desk | 2 | monitor or dock, spareOnly one is patched to a switch port. | IT |
Wiring
2 signal cables, 3 to outletsThe same at every desk.
List every cable
| Cable | From | To |
|---|---|---|
| Thunderbolt | Hub monitor, usb-c-2 | LaptopThunderbolt 4, 40 Gb/s, for two monitors |
| DisplayPort | Hub monitor, displayport-out-1 | Second monitor, fed over DisplayPort from the hub monitor, displayport-in-1Daisy chain |
| Cat 6 | Hub monitor, lan-1 | Data outlet 1, on the desk |
| Power | Hub monitor, power-in | Power outlet 1, on the desk |
| Power | Second monitor, fed over DisplayPort from the hub monitor, power-in | Power outlet 2, on the desk |